 GPL 121000 is a general purpose battery up to 10 years in 
standby service or more than 260 cycles at 100% discharge in 
cycle service . As with all CSB batteries, all are rechargeable , 
highly efficient , leak proof and maintenance free. 
  
  
下载专区 :GPL 121000规格书 
 | 
 
| 
   
 | 
 
| 
   
  
  
| 
 安培数 
 | 
 100Ah @ 20hr-rate to 1.75V per cell @25℃ (77°F) 
 | 
 
 
  
| 
 重量(kg)  
 | 
 Approx. 33.5 kg(73.86 lbs) 
 | 
 
 
  
| 
 最大放电电流5秒(A)  
 | 
 800A/130A(5sec) 
 | 
 
 
  
  
| 
 温度工作范围  
 | 
 Discharge: -15℃ ~50℃( 5 °F ~122°F ) 
Charge: -15℃ ~40℃ ( 5°F ~104°F ) 
Storage: -15℃ ~40℃ ( 5°F ~104°F ) 
 | 
 
 
  
| 
 一般使用温度工作范围  
 | 
 25℃±3℃(77°F±5°F) 
 | 
 
 
  
| 
 浮充使用充电条件  
 | 
 13.5 to 13.8 VDC/Unit Average at 25℃ (77°F) 
 | 
 
 
  
  
| 
 循环寿命测试条件  
 | 
 14.4 to 15.0 VDC/Unit Average at 25℃(77°F) 
 | 
 
 
  
| 
 单一放电条件  
 | 
 CSB Batteries can be stored for more than 6 months at 
25 (77 ). Please charge batteries before using. For 
higher temperatures the time interval will be shorter. 
 | 
 
 
  
| 
 端子  
 | 
 I2-Thread lead alloy recessed terminal to accept M6/M8 bolt 
 | 
 
 
  
| 
 电槽组材质  
 | 
 Polypropylene(UL 94-V0/File E50955)*Flammability resistance 
of (UL 94-HB/File E216959) can be available upon request. 
 | 
 
 
  
 | 
 
| 
   
 | 
 
| 
   
  
 | 
 
| 
   
 | 
 
| 
 定电流放电特性表 单位: 安培(25°C,77°F) 
 | 
 
 
  
| 
 终止电压/时间 
 | 
 5MIN  
 | 
 10MIN  
 | 
 15MIN  
 | 
 30MIN  
 | 
 1HR  
 | 
 2HR  
 | 
 3HR  
 | 
 4HR  
 | 
 5HR  
 | 
 8HR  
 | 
 10HR  
 | 
 20HR  
 | 
 
| 
 1.60V 
 | 
 423 
 | 
 277 
 | 
 212 
 | 
 127 
 | 
 73.0 
 | 
 41.1 
 | 
 29.1 
 | 
 22.8 
 | 
 18.9 
 | 
 12.2 
 | 
 10.0 
 | 
 5.28 
 | 
 
| 
 1.67V 
 | 
 375 
 | 
 266 
 | 
 207 
 | 
 125 
 | 
 72.4 
 | 
 40.7 
 | 
 29.0 
 | 
 22.7 
 | 
 18.8 
 | 
 12.1 
 | 
 9.93 
 | 
 5.23 
 | 
 
| 
 1.70V 
 | 
 355 
 | 
 258 
 | 
 203 
 | 
 124 
 | 
 71.8 
 | 
 40.6 
 | 
 28.7 
 | 
 22.6 
 | 
 18.6 
 | 
 12.0 
 | 
 9.89 
 | 
 5.21 
 | 
 
| 
 1.75V 
 | 
 317 
 | 
 240 
 | 
 194 
 | 
 120 
 | 
 71.1 
 | 
 40.2 
 | 
 28.6 
 | 
 22.4 
 | 
 18.5 
 | 
 11.9 
 | 
 9.82 
 | 
 5.19 
 | 
 
| 
 1.80V 
 | 
 283 
 | 
 219 
 | 
 183 
 | 
 115 
 | 
 68.9 
 | 
 39.3 
 | 
 27.9 
 | 
 22.0 
 | 
 18.2 
 | 
 11.8 
 | 
 9.66 
 | 
 5.10 
 | 
 
| 
 1.85V 
 | 
 245 
 | 
 196 
 | 
 164 
 | 
 106 
 | 
 65.2 
 | 
 37.6 
 | 
 26.8 
 | 
 21.2 
 | 
 17.4 
 | 
 11.4 
 | 
 9.45 
 | 
 4.92 
 | 
 
 
  
| 
 定功率放电特性表 单位: 瓦特(25°C,77°F) 
 | 
 
 
  
| 
 终止电压/时间 
 | 
 5MIN  
 | 
 10MIN  
 | 
 15MIN  
 | 
 30MIN  
 | 
 1HR  
 | 
 2HR  
 | 
 3HR  
 | 
 4HR  
 | 
 5HR  
 | 
 8HR  
 | 
 10HR  
 | 
 20HR  
 | 
 
| 
 1.60V 
 | 
 4,159 
 | 
 2,950 
 | 
 2,331 
 | 
 1,436 
 | 
 849 
 | 
 482 
 | 
 342 
 | 
 269 
 | 
 223 
 | 
 153 
 | 
 125 
 | 
 63.5 
 | 
 
| 
 1.67V 
 | 
 4,008 
 | 
 2,837 
 | 
 2,273 
 | 
 1,417 
 | 
 843 
 | 
 480 
 | 
 340 
 | 
 268 
 | 
 222 
 | 
 152 
 | 
 124 
 | 
 63.3 
 | 
 
| 
 1.70V 
 | 
 3,863 
 | 
 2,772 
 | 
 2,252 
 | 
 1,404 
 | 
 840 
 | 
 478 
 | 
 339 
 | 
 266 
 | 
 221 
 | 
 151 
 | 
 123 
 | 
 63.2 
 | 
 
| 
 1.75V 
 | 
 3,572 
 | 
 2,623 
 | 
 2,181 
 | 
 1,372 
 | 
 830 
 | 
 475 
 | 
 337 
 | 
 265 
 | 
 220 
 | 
 150 
 | 
 122 
 | 
 62.4 
 | 
 
| 
 1.80V 
 | 
 3,184 
 | 
 2,442 
 | 
 2,049 
 | 
 1,316 
 | 
 809 
 | 
 465 
 | 
 331 
 | 
 261 
 | 
 217 
 | 
 148 
 | 
 121 
 | 
 61.4 
 | 
 
| 
 1.85V 
 | 
 2,769 
 | 
 2,227 
 | 
 1,856 
 | 
 1,234 
 | 
 767 
 | 
 444 
 | 
 320 
 | 
 252 
 | 
 210 
 | 
 142 
 | 
 117 
 | 
 60.0 
 | 
 
 
 | 
 
 
 |